Skip to content
Holt Systems

Compressed air energy savings through compressor control

Several compressors each running on their own pressure switch idle, overlap and hold pressure higher than the plant needs. A sequencer runs them as one system.

Request a site assessment
Two motor-driven reciprocating air compressors in a plant room

Compressed air energy savings are among the most accessible energy savings in manufacturing and food plants, because compressed air is one of the most expensive forms of energy on site and most systems are not controlled as a whole. Where a site has two or more compressors, each typically runs on its own pressure switch, set slightly differently from the others. The result is compressors idling, several running part-loaded at the same time, and system pressure held higher than the plant needs.

How compressed air systems waste energy

The Australian Government’s compressed air guide notes that compressed air systems can consume up to 30% of a site’s electricity use, and that even in new systems, half of this energy can be lost through leaks. On multi-compressor sites, typical sources of waste include:

  • Idling compressors. A compressor running unloaded still draws a substantial share of its full-load power.
  • Overlapping operation. Two or more compressors running part-loaded at the same time, each less efficient than one fully loaded unit.
  • Excess pressure. A cascade of pressure switch settings pushes system pressure well above what equipment needs, increasing both compressor energy and leakage.
  • The wrong compressor trimming. A fixed-speed compressor modulating while a variable speed unit runs at full load.

Why individual pressure switches cannot coordinate

Each compressor’s controller only knows its own discharge pressure. To avoid all compressors starting and stopping together, their pressure bands are staggered, which means the system as a whole operates over a wide pressure band. No compressor knows what the others are doing, so none can decide that it is not needed.

Delivering compressed air energy savings with sequencing

A sequencer measures system pressure at one point and decides which compressors should run, which should be loaded and which should stop, holding pressure in a single narrow band.

Compressed air energy savings: sequencing and pressure control Pressure transmitter System pressure at the receiver orheader Sequencer Selects, loads and stopscompressors Compressors Base load units and one trim unit Air system Held in a narrow pressure band System pressure measured continuously
Compressed air energy savings: sequencing and pressure control

How it works

  1. 1

    Measure

    A single pressure transmitter measures system pressure where it matters, rather than at each compressor discharge.

  2. 2

    Base load

    Fixed-speed compressors run fully loaded to supply the base demand, in a rotated order so running hours are shared.

  3. 3

    Trim

    The most efficient part-load compressor, ideally variable speed, follows changes in demand.

  4. 4

    Stop and record

    Compressors that are not needed are stopped rather than left idling. Demand, pressure and running hours are logged.

The same guide reports that optimal sequencing of compressor units can save up to a third of compressed air system demand, and recommends using the most efficient part-load compressor for trimming and switching off idling compressors where feasible. Our scope covers compressor control. Air treatment equipment such as dryers and filters is outside it.

What it is worth

Compressors are also large contributors to a site’s peak electrical demand. Sequencing that avoids unnecessary starts can complement peak demand control.

Alternatives

  • Adjust the pressure switches. A useful first step, but switches still cannot coordinate compressors with each other.
  • The compressor manufacturer’s sequencer. A good choice where all compressors are from one manufacturer. Mixed fleets are where independent sequencing is most useful.
  • A new variable speed compressor. Often worthwhile, but without sequencing it can end up running alongside idling fixed-speed units.
  • A leak program alone. Always worthwhile, and complementary. It does not address idling, overlap or excess pressure.

How a project runs

Every project follows the same five stages. For a compressed air system, the assessment starts by measuring how the existing compressors actually run across a production week.

  1. 1

    Site assessment

    We log compressor loading, pressure and power across a representative period, and review the compressors, receivers, pipework layout and existing controls.

  2. 2

    Proposal

    A defined scope with a fixed price and program, and projected energy savings based on the logged data with the assumptions stated.

  3. 3

    Off-site build and test

    The sequencing panel and logic are built and tested off-site, including compressor rotation, standby and fault handling.

  4. 4

    Installation and commissioning

    Installation is completed during a planned stop, with each compressor's local control retained as a fallback until sequencing is proven.

  5. 5

    Handover and support

    Pressure bands are tuned in production, energy use is compared with the baseline, and you receive documentation and local support.

Why Holt Systems

Compressed air control is part of our energy controls service, designed around the compressors and demand pattern of your site.

Electrical, instrumentation and controls work is carried out under QLD Electrical Contractor Licence 1513082. Installations are completed to AS/NZS 3000 (the Wiring Rules), machine safety functions are designed with reference to AS/NZS 4024, and PLC programs are written in IEC 61131-3 languages and fully documented.

Manufacturer independent
We work across Siemens, Allen-Bradley (Rockwell Automation), Schneider Electric and Omron, and specify hardware on technical merit and local support availability.
Scoped to the requirement
Work is scoped to the specific machine, line or plant area, without the overheads of a large integrator, and quoted at a fixed price.
Reduced shutdown duration
Off-site build and testing means shutdown time is spent on installation and commissioning rather than fault-finding.
Single point of accountability
One accountable lead from site assessment through design, installation and handover.

Compressed air control questions

Do our compressors need to be the same brand?

No. Independent sequencing works with mixed brands and ages, using each compressor's remote load and run signals. Where a compressor has a network interface, more detailed status can also be read.

Does the system cover air dryers and filtration?

No. Our scope covers compressor control. Air treatment equipment such as dryers and filters remains with your existing arrangements and service providers.

How much pressure reduction is realistic?

That depends on the lowest pressure your equipment needs at the point of use and the pressure losses in your pipework. Logging during the assessment shows how much margin exists, and the proposal states the reduction assumed.

Will sequencing fix our leaks?

No, but it helps you find them. Logging shows the demand when production is stopped, which is largely leakage, and tracks whether it falls as leaks are repaired.

What happens if the sequencer fails?

Each compressor keeps its own local pressure control as a backup. If the sequencer loses control, compressors revert to local control and the plant keeps its air supply.

Is the saving guaranteed?

No. The saving depends on how your system currently runs. The proposal sets out projected savings from logged data, and energy use is compared with the baseline after commissioning.

Request a site assessment

Provide a brief outline of your site and requirements, and we will contact you to discuss the scope and arrange a site visit.

Or email hello@holtsystems.com.au

Your details are handled in accordance with our privacy policy.